9.1.1 SUMNER Cavity Checksheet - Timber Frame Exterior |
Project: |
Project: |
|
O.K √ |
Req'd √ |
Re Check |
O.K √ |
Re Check |
Date of O.K |
Operation: |
Operation: Full System for Timber frame Exterior |
|
Revision: |
Revision: F ( Manual 2014/08 ) |
|
|
Work Sequence |
Level/Zone |
|
Considerations |
Keep timber framing dry. Framing can have a maximum moisture content of no more than 18% to apply the stonework. As such we recommend using Kiln dried timber (14%-16% moisture) and wrapping the building asap. SUMNER Board acts as a rain shield so this should also be put in place asap. |
|
SUMNER CAVITY |
|
|
|
|
|
|
1.0 Framing Checks |
|
|
|
|
|
|
1.1 |
Check for double stud at window/door openings & internal corners |
|
|
|
|
|
1.2 |
Check alignment of framing i.e. Studs & nogs straight and true |
|
|
|
|
|
1.3 |
Upper framing aligning with lower framing |
|
|
|
|
|
1.4 |
Intermediate studs at centre < 600mm |
|
|
|
|
|
2.0 Air Seal |
|
|
|
|
|
|
2.1 |
Identify air seal |
|
|
|
|
|
|
2.1.1 Low wind loading < 1550 kpa, can be building wrap |
|
|
|
|
|
|
2.1.2 High wind loading > 1550 kpa, must be SUMNER Board |
|
|
|
|
|
|
2.1.3 Fire rated to -/30/30 & < 1550kpa, can be building wrap |
|
|
|
|
|
2.2 |
Roof Flashing |
|
|
|
|
|
|
|
|
2.2.1 Fit lower roof flashings intersecting with upper framing with |
|
|
|
|
|
|
|
|
upstand behind building wrap & stop ended where necessary |
|
|
|
|
|
|
|
2.3 |
Building wrap |
|
|
|
|
|
|
2.3.1 Fixed with staples. Fix blue band (Polyprop Tape) vertically |
|
|
|
|
|
|
between studs> 300 cts or horizontally between nogs |
|
|
|
|
|
|
|
|
2.3.2 Repair all cuts & tears with duct tape |
|
|
|
|
|
|
2.3.3 Fold in around windows ( 4 sides) |
|
|
|
|
|
|
2.3.4 Tape the 4 corners and sill of each opening with SUMNER tape. |
|
|
|
|
|
|
|
2.4 |
Rigid backer |
|
|
|
|
|
|
2.4.1 Fix with 40mm clouts at 300 centres to all nogs & studs |
|
|
|
|
|
|
2.4.2 Edge distances; min 15.0mm |
|
|
|
|
|
|
Corner distances; min 100 & 50 |
|
|
|
|
|
|
2.4.3 Perimeter seal with SUMNER Tape |
|
|
|
|
|
|
2.4.4 Tape the 4 corners and sill of each opening with SUMNER tape. |
|
|
|
|
|
|
|
3.0 Batten & Flashing |
|
|
|
|
|
|
3.1 |
Fixings - Tack in place with 40.mm fixings |
|
|
|
|
|
3.2 |
Set out horizontal battens |
|
|
|
|
|
|
3.2.1 Top (set 10.0mm below horizontal protrusion) |
|
|
|
|
|
|
3.2.2 Bottom (set flush with bottom plate) |
|
|
|
|
|
|
3.2.3 Fit horizontal batten to bottom of full Ht. windows/doors with top |
|
|
|
|
|
|
|
|
of batten flush with top of floor or retro fit aluminium angle |
|
|
|
|
|
|
|
3.3 |
Fitting flashings |
|
|
|
|
|
|
3.3.1 Vermin flashing to bottom batten |
|
|
|
|
|
|
3.3.2 Fit head and sill tray flashing over windows (extend past |
|
|
|
|
|
|
by 50mm) including assembling Stop Ends |
|
|
|
|
|
|
3.3.3 Building wrap sits into head flashing |
|
|
|
|
|
3.4 |
Fit off remainder of batten |
|
|
|
|
|
|
3.4.1 Horizontal above window |
|
|
|
|
|
|
3.4.2 Horizontal below window |
|
|
|
|
|
|
3.4.3 Vertical at window is set back 10mm |
|
|
|
|
|
|
3.4.4 Verticals at all sheet joins |
|
|
|
|
|
|
3.4.5 Verticals at all intermediate studs (max 600 cts) |
|
|
|
|
|
|
3.4.6 Horizontals at all horizontal joints & nogs |
|
|
|
|
|
|
3.4.7 Horizontals at inter-storey reter to specific detail |
|
|
|
|
|
3.5 |
Penetrations |
|
|
|
|
|
|
|
|
3.5.1 Fit meter box using SUMNER tape flash to all 4 sides of penetration |
|
|
|
|
|
|
|
|
3.5.2 Install all pipe & duct penetrations and seal as with site folded SUMNER tape gasket |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SUMNER BOARD |
|
|
|
|
|
|
|
|
4.1 |
Fixing Board |
|
|
|
|
|
|
|
|
4.1.1 Sheets to over-sail bottom plate by 50.0mm |
|
|
|
|
|
|
|
|
4.1.2 Maintain ground clearances. Bottom of sheets to finish 35.0 mm clear |
|
|
|
|
|
|
|
|
of finished deck surface or 100.0 mm clear of paved surfaces |
|
|
|
|
|
|
|
|
or 175.0 mm clear of unpaved surfaces |
|
|
|
|
|
|
|
|
4.1.3 9.0mm fix with 60mm stainless steel screws |
|
|
|
|
|
|
|
|
4.1.4 Normal weight system, centres max 220mm to perimeter, centre stud and nogs |
|
|
|
|
|
|
|
|
4.1.4 Heavy Weight System centres max 180mm to perimeter, centre stud and nogs (SUMNER Otago and Bluestone Series only) |
|
|
|
|
|
|
|
|
4.1.5 Heads NOT flush with face of sheet - ie leave 2mm proud |
|
|
|
|
|
|
|
|
4.1.6 Window flashings stop ended ( Sealant if PVC ) |
|
|
|
|
|
|
|
|
4.1.7. Install Air Seal to window trim gap prior to fixing interior lining |
|
|
|
|
|
|
|
CONTROL JOINTS |
4.1.8 Provide for vertical control joints @ 5m centers max, and horizontal control joints at max 8 m centers |
|
|
|
|
|
|
|
|
Nominate type: SUMNER Ledgestone Series □ |
|
|
|
|
|
|
SUMNER Otago Series □ |
|
|
|
|
|
|
SUMNER Traditional Series □ |
|
|
|
|
|
|
SUMNER Bluestone Series □ |
|
|
|
|
|
|
SUMNER Sandstone Series □ |
|
|
|
|
|
NAME OF BUILDER: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ |
|
|
|
|
|
|
|
BUILDERS LBP Number: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ |
|
|
|
|
|
|
|
PLEASE SIGN HERE |
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ |
Date: |
|
|
|
|
|
|
|
Note: This form is a legal document and you will be held liable for the costs of any failures, whether direct or indirect, due to falsifications in the document. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|